Adesign works in strict conjunction with the following SANS codes and By-Laws:

•  LPG Domestic and Commercial Installations (Manifolds) SANS 10087-1

 

>  Cylinder/s to be a minimum horizontal distance of 1m away from any window, door or airbrick.
>   Any window above a cylinder must be minimum 3m or a non-combustible roof must be provided to reduce the 

      vertical distance to 300mm, however the distance from the cylinder valve to the window must be 1.5m.  

>   Any electrical installation must be 5m away from the LPG installation.

>   No drains shall be located within 2m radius of the LPG installation. 

>   An outdoor light may be 1.5m above the LPG installation.


 


  LPG Industrial Installations (Bulk Tank / Depot) SANS 10087-3


  LPG Cylinder Filling and Storage - SANS 10087-7



Above Ground Petroleum Installations – SANS 10131
Above Ground Bulk Petroleum Installations – SANS 10089-1
Underground Petroleum Installations – SANS 10089-3